Tri Rated Cable , Single core PVC Insulated 105°C

Tri Rated Cable, Single Core

Applications

  • Used for internal wiring in many applications such as Control panels, switch – gears, Motor starters etc.
  • Tri – rated cables also referred to BS 6231 wires, H05V2-K / H07V2-K Cables or Panel wires.
Tri Rated Cable, Single Core Product Construction

Features

  • Flame retardant
  • Heat resistant, 105 °C continuously rated
  • Tri-rated: UL 1015, CSA 22.2 and BS 6231 specifications
  • Flexible, RoHS compliant
  • Flexible Strand Structure.
Balajiwires Quick Quote

Technical Data

Standard 1.UL 1015                 2.CSA 22.2                    3.BS 6231
Rated Voltage ( U0 / U ) i) UL, CSA : 450/ 750V
ii) BS 6231: 600/1000V
iii) BS EN 50525 – 2- 31 : 300/500V, 450/750V
Temperature rating i) UL, CSA : +105°C
ii) BS 6231 : +90°C
iii) Minimum : -15°C
Bending Radius (min) 6 x overall diameter
Download Product Details

Certifications & Compliance

Tri Rated Cable, Single Core Certifications & Compliance

Cable Design Parameters

Nominal Cross sectional ( In sq mm ) Strand dia
(mm)
Max.
Nominal insulation thickness (mm)
Nom.
Nominal outer diameter of cable (mm)
Nom.
Max conductor resistance at  20°C (mΩ/m)
0.5 0.21 0.8 2.70 39.0
0.75 0.21 0.8 2.85 26.0
1 0.21 0.8 3.00 19.5
1.5 0.26 0.8 3.30 13.3
2.5 0.26 0.8 3.75 7.98
4 0.31 0.8 4.35 4.95
6 0.31 0.8 4.85 3.30
10 0.41 1.0 6.30 1.91
16 0.41 1.0 8.10 1.21
25 0.41 1.2 9.40 0.780
35 0.41 1.2 10.90 0.554
50 0.41 1.4 13.10 0.386
70 0.51 1.4 15.10 0.272
95 0.51 1.6 16.10 0.206
120 0.51 1.6 17.90 0.161
150 0.51 1.8 20.20 0.129
185 0.51 2.0 22.85 0.106
240 0.51 2.2 24.40 0.0801

Disclaimer :

REACH compliance should be considered as customer specific requirement and must be specified at time enquiry if required. The information contained in this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting the cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.