H05V-K Cables

Single Core UL-1007

Applications

  • Cable designed for internal wiring in switch control,
    relay and Instrumentation panels of power
    switchgear.
  • Used as static appliances, internal connectors in
    rectifier equipment, motor starter and controller.
Single Core UL-1007 Product Construction

Features

  • PVC self-extinguishing and flame retardant
    according to EN 60332-1-2.
Balajiwires Quick Quote

Technical Data

Download Product Details

Certifications & Compliance

Single Core UL-1007 Certifications & Compliance

Cable Design Parameters

Part No. Size (sqmm) Construction Conductor Resistance (Ω/km) Sheath Thickness (mm)
Outer Diameter (mm)
CB-2.50 2.5 48/0.26 Max: 7.98 Nominal: 0.80
Max: 4.10 / Min: 3.40
CB-0.5 0.5 16/0.21 Max: 39.00 Nominal: 0.60 Max: 2.60
CB-0.75 0.75 24/0.21 Max: 26.00 Nominal: 0.60 Max: 2.80
CB-1.00 1 32/0.21 Max: 19.50 Nominal: 0.60 Max: 3.00
CB-1.50 1.5 30/0.26 Max: 13.30 Nominal: 0.60 Max: 3.40
CB-2.50 2.5 50/0.26 Max: 7.98 Nominal: 0.70 Max: 4.10
CB-4.00 4 56/0.31 Max: 4.95 Nominal: 0.80 Max: 4.80
CB-6.00 6 84/0.31 Max: 3.30 Nominal: 0.80 Max: 5.30
CB-10.00 10 80/0.41 Max: 1.91 Nominal: 1.00 Max: 7.00
CB-16.00 16 126/0.40 Max: 1.21 Nominal: 1.00 Max: 8.10
CB-25.00 25 196/0.39 Max: 0.780 Nominal: 1.20 Max: 10.20
CB-35.00 35 276/0.41 Max: 0.554 Nominal: 1.20 Max: 11.70
CB-50.00 50 703/0.30 Max: 0.386 Nominal: 1.40 Max: 13.90
CB-70.00 70 360/0.50 Max: 0.272 Nominal: 1.40 Max: 16.00
CB-95.00 95 475/0.45 Max: 0.206 Nominal: 1.40 Max: 18.20
CB-120.00 120 608/0.51 Max: 0.161 Nominal: 1.60 Max: 20.20
CB-150.00 150 741/0.51 Max: 0.129 Nominal: 1.80 Max: 22.50

Disclaimer :

The information contained in this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting the cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.