UL-1569, Single Core UL-1569 105°C Cables
Applications
- Appliance wiring material (AWM)
- Internal wiring of meters, panels, Machine Tool electrical & electronic equipment, In Machine Laid, In protective tubes, flexible pipes and also for Motors and Transformers.
Features
- PVC self – extinguishing and flame retardant, test method to UL VW-1 and CSA FT 1 / FT 2
- Rated for Continuous use up to 60°C or 80°C in oil and 105°C in Dry.
Technical Data
Standard | UL – Std. 758. Complies to CSA No. 22.2 210 |
Nominal Voltage | 300 V |
Test Voltage (Spark Test) | AWG 28 to 24 → 4 kV (DC) AWG 22 to 20 → 5 kV (DC)AWG 18 to 16 → 6 KV (DC) ≤ AWG 8 → 7.5 kV (DC) |
Temperature Range | Flexible -5°C to +105°C
Fixed Installation -20°C to +105°C |
Temperature at Conductor | Max. UL and CSA : +105°C |
Bending Radius | Flexing 10 x Cable ø .Fixed Installation 5 x cable ø |
Certifications & Compliance
Cable Design Parameters
AWG | Metric Cross Sectional Area (Sq .mm ) | No of Strand /Strand Diameter (mm) | Approx. Diameter of Conductor | Average Insulation Thickness | Minimum Insulation Thickness | Nominal Cable Diameter |
28 | 0.0804 | 7/0.13 | 0.385 | 0.39 | 0.33 | 1.20 |
26 | 0.128 | 7/0.16 | 0.485 | 0.39 | 0.33 | 1.30 |
24 | 0.205 | 7/0.20 | 0.610 | 0.39 | 0.33 | 1.45 |
22 | 0.324 | 7/0.25 | 0.760 | 0.39 | 0.33 | 1.60 |
20 | 0.519 | 7/0.31 | 0.950 | 0.39 | 0.33 | 1.80 |
20 | 0.519 | 26/0.16 | 0.950 | 0.39 | 0.33 | 1.80± 0.10 |
20 | 0.519 | 19/0.19 | 0.950 | 0.39 | 0.33 | 1.78 ± 0.10 |
18 | 0.823 | 16/0.26 | 1.20 | 0.39 | 0.33 | 2.00 |
16 | 1.317 | 26/0.26 | 1.55 | 0.39 | 0.33 | 2.35 |
14 | 2.078 | 41/0.26 | 1.90 | 0.39 | 0.33 | 2.70 |
12 | 3.31 | 65/0.26 | 2.40 | 0.39 | 0.33 | 3.20 |
10 | 5.26 | 105/0.26 | 3.05 | 0.39 | 0.33 | 3.85 |
8 | 8.367 | 168/0.26 | 3.90 | 0.77 | 0.69 | 5.40 |
8 | 8.367 | 1083/0.10 | 3.90 | 0.77 | 0.69 | 5.40 |
6 | 13.30 | 266/0.26 | 4.85 | 0.77 | 0.69 | 6.40 |
4 | 21.15 | 420/0.26 | 6.10 | 0.77 | 0.69 | 7.65 |
2 | 33.62 | 665/0.26 | 7.65 | 0.77 | 0.69 | 9.20 |
Disclaimer :
REACH compliance should be considered as customer specific requirement and must be specified at time enquiry if required. The information contained in this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is believed to be correct at the time of publication. When selecting the cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.